# Division 28: Electronic Safety and Security submittal deviations

> Source: https://deviationcheck.com/divisions/28-electronic-safety-security/
> Deviation Check - AI submittal review for General Contractors (Aliso LLC).

Division 28 covers electronic safety and security systems in commercial construction: fire detection and alarm, mass notification, access control, video surveillance, and intrusion detection. Common CSI sections submitted for review:

## Common Division 28 CSI sections

- 28 05 00 - Common Work Results for Electronic Safety and Security
- 28 08 00 - Commissioning of Electronic Safety and Security
- 28 10 00 - Electronic Access Control and Intrusion Detection
- 28 13 00 - Access Control
- 28 16 00 - Intrusion Detection
- 28 20 00 - Electronic Surveillance
- 28 23 00 - Video Surveillance
- 28 30 00 - Electronic Detection and Alarm
- 28 31 00 - Fire Detection and Alarm
- 28 31 11 - Digital, Addressable Fire-Alarm Systems
- 28 31 33 - Fire Detection Sensors (smoke, heat, duct, beam)
- 28 31 43 - Fire-Alarm Notification Appliances (horns, strobes, speakers)
- 28 31 49 - Carbon-Monoxide Detection
- 28 46 00 - Fire Detection and Alarm Interfaces (elevator recall, HVAC shutdown, door release)

## The six deviation categories in Division 28 Electronic Safety and Security

### Manufacturer or Product Substitution (default grade: Blocker)

The submittal proposes a different manufacturer or product than the spec names, without an approved or-equal or substitution request.

Fire alarm and security specs name specific system manufacturers. Mixed-manufacturer systems often create compatibility issues. Look for:
- Fire alarm control panel (FACP) manufacturer substitutions (Notifier/Honeywell, EST/Edwards/Carrier, Simplex/Johnson Controls, Siemens, Bosch, Silent Knight)
- Initiating device manufacturer (detectors, pull stations) must match FACP manufacturer for addressable systems
- Notification appliance manufacturer substitutions (System Sensor, Wheelock/Eaton, Gentex, Amseco)
- Access control system manufacturer substitutions (Lenel/Carrier, Software House, Genetec, Honeywell, HID)
- Video surveillance manufacturer substitutions (Axis, Hanwha/Samsung, Bosch, Pelco, Avigilon/Motorola)
- Intrusion detection panel substitutions (Bosch, DMP, Honeywell Vista/Ademco)
- Card reader and credential manufacturer substitutions (HID, ASSA ABLOY)
- Mass notification system manufacturer substitutions (Notifier, EST, AtlasIED)

Full guide: https://deviationcheck.com/divisions/28-electronic-safety-security/manufacturer-substitution/

### Performance Specification Gap (default grade: Blocker)

A measurable performance property in the submittal (rating, capacity, tolerance, efficiency) does not meet what the spec requires.

Key performance parameters in Div 28 submittals:
- **Fire alarm system type** (conventional vs addressable, single-stage vs two-stage)
- **Notification appliance candela rating** (15, 30, 75, 110, 135, 185 cd per NFPA 72 Table 18.5.4.3.1)
- **Notification appliance dBA rating** (minimum 15 dBA above ambient or 5 dBA above max, per NFPA 72)
- **Smoke detector sensitivity range** (per NFPA 72, UL 268, typically 0.5-4.0 %/ft obscuration)
- **Duct detector air velocity range** (fpm per NFPA 72/90A)
- **System capacity** (number of addressable points, zones, loops for FACP)
- **Camera resolution** (megapixels, pixels per foot at target distance)
- **Camera frame rate** (fps at stated resolution)
- **Camera low-light performance** (minimum illumination in lux)
- **Camera storage retention** (days at stated resolution and frame rate)
- **Access control panel capacity** (doors, readers, cardholders per panel/server)
- **Card reader technology** (proximity 125kHz, smart card 13.56MHz, mobile credential, biometric)
- **Battery standby time** (24 hours for fire alarm per NFPA 72, longer for some security systems)
- **Pathway survivability** (Level 0, 1, 2, 3 per NFPA 72 Chapter 12)

Full guide: https://deviationcheck.com/divisions/28-electronic-safety-security/performance-specification-gap/

### Missing Certification or Compliance Documentation (default grade: Fix and Resubmit)

A required listing, test report, certification, or compliance document is absent from the submittal package.

Required certifications in Div 28 submittals:
- **UL listing** for fire alarm equipment (UL 864 for FACP, UL 268 for smoke detectors, UL 217, UL 521 for heat detectors, UL 2572 for mass notification)
- **NFPA 72** compliance (National Fire Alarm and Signaling Code)
- **NFPA 70 (NEC)** compliance for wiring
- **UL 294** listing for access control (standard for access control system units)
- **UL 1076** listing for intrusion detection (proprietary burglar alarm)
- **AHJ approval** documentation (fire marshal review/approval of fire alarm shop drawings)
- **NICET certification** for fire alarm system designer (Level II-IV per spec)
- **Factory certification** for installing contractor (manufacturer-authorized dealer/installer)
- **Compatibility listing** documentation (devices listed compatible with specified FACP)
- **Battery calculation** documentation (standby and alarm load per NFPA 72)
- **Voltage drop calculations** for notification appliance circuits
- **Sequence of operations** matrix
- **ADA compliance** for notification appliances (visible signals per NFPA 72 and ADA)
- **NDAA/TAA compliance** for video surveillance equipment (Section 889, critical for government projects)
- **FCC certification** for wireless devices

Full guide: https://deviationcheck.com/divisions/28-electronic-safety-security/missing-certification/

### Aesthetic Deviation (default grade: Fix and Resubmit)

A visible attribute (color, finish, texture, profile) differs from the spec or the architect-approved sample.

- Notification appliance color (white, red) and mounting style (wall, ceiling)
- Camera housing style and color (dome, bullet, turret, PTZ)
- Card reader style, color, and mounting (mullion, single-gang, surface)
- Pull station color (red is code-required for fire alarm)
- Intercom/speaker style and finish
- Keypad style and color

Full guide: https://deviationcheck.com/divisions/28-electronic-safety-security/aesthetic-deviation/

### Detail or Installation Mismatch (default grade: Fix and Resubmit)

The submitted detail, dimension, anchorage, or installation method differs from what the spec or drawings require.

- **Detector spacing** exceeds NFPA 72 maximum for ceiling height and type
- **Notification appliance placement** does not meet NFPA 72 visible/audible coverage requirements
- **Conductor size** (gauge) or type differs from spec (fire alarm circuits require specific wire: FPLP, FPLR per NEC)
- **Conduit type** mismatch for fire alarm circuits (often requires EMT minimum, some specs require rigid)
- **Pathway survivability level** below spec requirement (Level 2 vs Level 1)
- **Camera mounting height or angle** differs from design
- **Camera lens focal length** does not achieve specified pixels per foot at target distance
- **Card reader mounting height** differs from ADA requirement (48" max per ADA)
- **Door contact type** mismatch (recessed vs surface, wide-gap vs standard)
- **End-of-line resistor value** mismatch with FACP requirements
- **Elevator recall interface** wiring or sequence differs from ASME A17.1/NFPA 72 requirements
- **HVAC shutdown interface** relay location or wiring differs

Full guide: https://deviationcheck.com/divisions/28-electronic-safety-security/detail-installation-mismatch/

### Submittal Package Incompleteness (default grade: Fix and Resubmit)

A required submittal element (cut sheet, schedule, calculation, sample) is missing, leaving the package unreviewable as submitted.

Commonly required items in Div 28 specs:
- Fire alarm shop drawings (floor plans with device locations, riser diagrams, panel wiring)
- Sequence of operations matrix (input/output, cause and effect)
- Battery calculations per NFPA 72
- Voltage drop calculations for NAC circuits
- Device compatibility listing with FACP
- Point-to-point wiring diagrams
- Camera layout drawings with field-of-view diagrams
- Network architecture diagram (for IP-based systems)
- Storage calculations (camera count x resolution x frame rate x retention days)
- Access control riser diagram
- Door hardware schedule coordination (electrified hardware, locks, contacts, REX)
- NICET designer certification
- Contractor factory certification/authorization letter
- AHJ-required permit application documentation
- Programming and commissioning plan

---

Full guide: https://deviationcheck.com/divisions/28-electronic-safety-security/submittal-package-incompleteness/

## How Division 28 deviations are graded

- **Missing UL 864 listing for FACP:** BLOCKER (NFPA 72, code requirement)
- **Notification appliance candela below NFPA 72 requirement for room size:** BLOCKER (life-safety, ADA)
- **Smoke detector spacing exceeds NFPA 72 maximum:** BLOCKER (inadequate coverage)
- **Fire alarm device not compatible with specified FACP:** BLOCKER (system will not function)
- **Missing AHJ approval for fire alarm drawings:** BLOCKER (cannot install without approval)
- **Missing NICET certification where spec requires:** BLOCKER (designer qualification)
- **Battery standby time below NFPA 72 requirement (24 hours + 5 min alarm):** BLOCKER (code)
- **NDAA/TAA non-compliant cameras on government project:** BLOCKER (Federal law)
- **Pathway survivability below spec level:** BLOCKER if high-rise or institutional, FIX_AND_RESUBMIT otherwise
- **Camera resolution below spec at target distance:** FIX_AND_RESUBMIT (surveillance adequacy)
- **Card reader technology mismatch (prox where smart card specified):** FIX_AND_RESUBMIT (security level)
- **Missing sequence of operations matrix:** FIX_AND_RESUBMIT (coordination, cannot program without it)
- **Notification appliance color mismatch:** FIX_AND_RESUBMIT (aesthetic)