# Missing Certification or Compliance Documentation in Division 25 Integrated Automation submittals

> Source: https://deviationcheck.com/divisions/25-integrated-automation/missing-certification/

A required listing, test report, certification, or compliance document is absent from the submittal package.

## What to look for in Division 25 Integrated Automation

Required certifications in integrated automation submittals:
- **UL 916** listing for energy management equipment - absence is a blocker
- **UL 864** listing where controllers interface with fire alarm systems
- **BACnet Testing Laboratories (BTL) listing** confirming protocol conformance class
- **LonMark certification** for LonWorks-based devices
- **ASHRAE Standard 135** compliance statement for BACnet devices
- **ASHRAE Guideline 13** conformance for DDC system specification
- **IEC 61131-3** compliance for PLC programming languages used in controllers
- **NEMA standards** compliance for enclosures housing automation equipment
- **NIST cybersecurity framework** alignment documentation for networked building systems
- **ENERGY STAR** building certification data where spec requires
- **FCC Part 15** compliance for wireless sensors and devices
- **Seismic certification** (IBC, OSHPD) for controller panel anchorage where required
- **Factory acceptance test (FAT) reports** for head-end servers and controllers

## Severity

Default grade: Fix and Resubmit. Escalates to Blocker when the missing document is a code or life-safety requirement (UL listing, fire rating).