Division 13 Special Construction
Missing Certification or Compliance Documentation in Division 13 Special Construction submittals
Short answer
A required listing, test report, certification, or compliance document is absent from the submittal package. Default grade in Division 13 Special Construction: Fix and Resubmit.
A required listing, test report, certification, or compliance document is absent from the submittal package. This guide covers how it shows up specifically in Division 13 Special Construction submittals.
What to look for in Division 13 Special Construction
Required certifications in Div 13 submittals:
- UL 96A listing for lightning protection components
- NFPA 780 compliance documentation for lightning protection system design
- ISO 14644 clean room classification test protocol and certification plan
- ASHRAE 90.1/189.1 energy compliance for controlled environment enclosures
- IBC Chapter 30 and local health department compliance for aquatic facilities
- ASTM E90/E413 test reports for sound-rated room assemblies
- ASTM C1166 flame propagation test report for clean room panels
- NRC (Nuclear Regulatory Commission) approval for radiation shielding materials
- ICC 500 certification for storm shelters
- FEMA P-361 compliance documentation for safe rooms
- ASCE 7 seismic design basis and isolation system qualification test reports
- FM Approvals for insulated metal panels (fire, wind)
- UL listing for vault doors and modular vault systems
- IAS (International Accreditation Service) or equivalent for metal building fabricator
- AWS D1.1 welding certifications for pre-engineered structures
How severe is it?
Default grade: Fix and Resubmit. Escalates to Blocker when the missing document is a code or life-safety requirement (UL listing, fire rating).
Deviation Check assigns a default per category and escalates or de-escalates based on the spec, always showing its reasoning. See the Division 13 severity rules.
What the PM should do
Stamp the submittal Revise and Resubmit. Mark the deviation, return the relevant spec passage as a redline, and have the sub correct and re-send before fabrication or installation.
Other deviation categories in Division 13
Frequently asked questions
What certifications are required in Division 13 Special Construction submittals for lightning protection systems?
The submittal must include a UL 96A listing for all lightning protection components and NFPA 780 compliance documentation for the system design. Without both, the package is incomplete and escalates to a Blocker because these are code and life-safety requirements. A design drawing with zone of coverage analysis should also be present before the PM can fully evaluate the system.
Does a Division 13 storm shelter submittal need to include ICC 500 and FEMA documentation?
Yes. The submittal must include ICC 500 certification for the shelter and FEMA P-361 compliance documentation for safe rooms. These are the governing standards for wind speed and missile impact criteria. The absence of either document escalates the missing-certification flag to a Blocker. AWS D1.1 welding certifications for pre-engineered structures and IAS fabricator accreditation are also required items that subcontractors frequently omit on first submission.