# Division 07: Thermal and Moisture Protection submittal deviations

> Source: https://deviationcheck.com/divisions/07-thermal-moisture-protection/
> Deviation Check - AI submittal review for General Contractors (Aliso LLC).

Division 07 covers thermal and moisture protection systems in commercial construction: waterproofing, insulation, air/vapor barriers, roofing, flashing, fireproofing, firestopping, and joint sealants. Common CSI sections submitted for review:

## Common Division 07 CSI sections

- 07 11 00 - Dampproofing
- 07 13 00 - Sheet Waterproofing
- 07 14 00 - Fluid-Applied Waterproofing
- 07 21 00 - Thermal Insulation
- 07 21 13 - Board Insulation
- 07 21 16 - Blanket Insulation
- 07 21 29 - Sprayed Insulation
- 07 25 00 - Weather Barriers (air barriers, vapor retarders, WRB)
- 07 27 00 - Air Barriers
- 07 41 13 - Metal Roof Panels (standing seam)
- 07 52 00 - Modified Bituminous Membrane Roofing
- 07 53 00 - Elastomeric Membrane Roofing (EPDM, TPO, PVC)
- 07 54 00 - Thermoplastic Membrane Roofing
- 07 62 00 - Sheet Metal Flashing and Trim
- 07 81 00 - Applied Fireproofing
- 07 84 00 - Firestopping
- 07 92 00 - Joint Sealants

## The six deviation categories in Division 07 Thermal and Moisture Protection

### Manufacturer or Product Substitution (default grade: Blocker)

The submittal proposes a different manufacturer or product than the spec names, without an approved or-equal or substitution request.

Div 07 specs routinely name roofing system manufacturers, waterproofing producers, and insulation brands. Look for:
- Roofing membrane manufacturer substitutions (Carlisle, Firestone/Elevate, Johns Manville, GAF, Sika Sarnafil, Tremco)
- Waterproofing manufacturer substitutions (Carlisle CCW, W.R. Grace/GCP, Henry Company, Tremco, Cetco)
- Insulation manufacturer changes (Owens Corning, Johns Manville, Rockwool/Roxul, Dow/DuPont, Carlisle)
- Air barrier manufacturer substitutions (Henry Blueskin, Grace Perm-A-Barrier, Carlisle CCW, Prosoco)
- Fireproofing manufacturer substitutions (Isolatek/Cafco, W.R. Grace/Monokote, Southwest Fireproofing, Carboline)
- Firestop system manufacturer substitutions (Hilti, 3M, STI, Specified Technologies)
- Sealant manufacturer changes (Dow, Tremco, Pecora, Sika, Bostik)
- Metal panel manufacturer substitutions (ATAS, Centria, Kingspan, Morin)

Full guide: https://deviationcheck.com/divisions/07-thermal-moisture-protection/manufacturer-substitution/

### Performance Specification Gap (default grade: Blocker)

A measurable performance property in the submittal (rating, capacity, tolerance, efficiency) does not meet what the spec requires.

Key performance parameters in Div 07 submittals:
- **R-value** per inch and total assembly thermal resistance (per ASHRAE 90.1 / IECC)
- **Wind uplift rating** (FM 1-60, 1-90, 1-120, 1-150, 1-180 or UL 580 classification)
- **Fire rating** (ASTM E119 hours for fireproofing, UL fire resistance assembly listing)
- **Flame spread / smoke development** (ASTM E84 Class A/B/C, NFPA 285 for wall assemblies)
- **Water vapor permeance** (perms per ASTM E96, vapor barrier vs vapor retarder classification)
- **Air leakage rate** (cfm/sf at 1.57 psf per ASTM E2357 for air barriers)
- **Membrane thickness** (mils for single-ply, plies for built-up/modified bitumen)
- **Peel adhesion** (pli for self-adhered membranes)
- **Elongation percentage** (ASTM D412 for elastomeric membranes)
- **Tensile strength** (psi for membranes)
- **Shore A hardness** (for sealants)
- **Joint movement capability** (+/- % for sealants)
- **STC (Sound Transmission Class)** for assembly (where specified)
- **Fireproofing density** (pcf for sprayed fireproofing)
- **Fireproofing thickness** per UL assembly listing and structural member size

Full guide: https://deviationcheck.com/divisions/07-thermal-moisture-protection/performance-specification-gap/

### Missing Certification or Compliance Documentation (default grade: Fix and Resubmit)

A required listing, test report, certification, or compliance document is absent from the submittal package.

Required certifications in Div 07 submittals:
- **FM Approvals** (Factory Mutual) for roof assemblies (wind uplift, fire, hail)
- **UL listing** for fire-rated assemblies, firestop systems
- **UL/WHI (Warnock Hersey Intertek)** fire resistance assembly listings
- **NRCA (National Roofing Contractors Association)** compliance
- **ASTM test reports** (E96 vapor permeance, E84 flame spread, D4541 adhesion, C518/C177 thermal, E2357 air leakage, E1886/E1996 wind-borne debris)
- **ICC-ES ESR** for proprietary systems (air barriers, insulation systems)
- **NFPA 285** test report for exterior wall assemblies with combustible components
- **Manufacturer system warranty letter** (NDL - No Dollar Limit, or limited)
- **Roof system warranty application** (10/15/20/25/30 year terms)
- **Manufacturer's inspection letter** (pre-warranty inspection)
- **SPFA (Spray Polyurethane Foam Alliance)** certification for SPF applicators
- **ABAA (Air Barrier Association of America)** certification for air barrier installers
- **LEED documentation** (recycled content, SRI for cool roofs, regional materials)

Full guide: https://deviationcheck.com/divisions/07-thermal-moisture-protection/missing-certification/

### Aesthetic Deviation (default grade: Fix and Resubmit)

A visible attribute (color, finish, texture, profile) differs from the spec or the architect-approved sample.

- Roofing membrane color (white, tan, gray - affects SRI/cool roof compliance)
- Metal roof panel color and profile
- Flashing and trim color
- Sealant color (per architect's schedule)
- Exposed insulation finish (where architecturally exposed)
- Wall panel color and texture

Full guide: https://deviationcheck.com/divisions/07-thermal-moisture-protection/aesthetic-deviation/

### Detail or Installation Mismatch (default grade: Fix and Resubmit)

The submitted detail, dimension, anchorage, or installation method differs from what the spec or drawings require.

- **Membrane thickness** below manufacturer warranty minimum
- **Insulation board thickness** or layering sequence differs
- **Lap width or seam method** (heat weld vs adhesive vs tape vs liquid-applied)
- **Flashing termination detail** (reglet vs surface-mount counterflashing, termination bar)
- **Roof drain type or size** differs
- **Fastening pattern** (mechanically attached vs fully adhered vs ballasted)
- **Attachment method** for insulation (adhesive vs mechanical vs both)
- **Fireproofing thickness** differs from UL listed assembly requirement
- **Firestop system configuration** differs from tested/listed assembly (UL/WHI)
- **Sealant joint width-to-depth ratio** outside manufacturer recommendations
- **Vapor retarder location** in wall/roof assembly (warm side vs wrong side)
- **Air barrier continuity detail** at transitions (wall-to-roof, wall-to-foundation)
- **Metal panel attachment** clip type or spacing differs

Full guide: https://deviationcheck.com/divisions/07-thermal-moisture-protection/detail-installation-mismatch/

### Submittal Package Incompleteness (default grade: Fix and Resubmit)

A required submittal element (cut sheet, schedule, calculation, sample) is missing, leaving the package unreviewable as submitted.

Commonly required items in Div 07 specs:
- Roof system warranty application with coverage terms
- Manufacturer's pre-installation inspection letter
- FM Approval or UL listing documentation for roof assembly
- Wind uplift calculations for the specific building and zone
- Insulation product data with R-value and fire test results
- Air barrier product data with permeance and adhesion test results
- Firestop system detail drawings matching UL/WHI listing
- Fireproofing thickness schedule by structural member size and fire rating
- Sealant compatibility test results (where spec requires)
- Core samples and moisture survey (for re-roofing projects)
- Installer qualification documentation (manufacturer-certified applicator)
- Mock-up or field sample requirements
- Maintenance plan for roof system warranty compliance

---

Full guide: https://deviationcheck.com/divisions/07-thermal-moisture-protection/submittal-package-incompleteness/

## How Division 07 deviations are graded

- **R-value below ASHRAE 90.1 or IECC minimum:** BLOCKER (energy code violation)
- **Missing FM or UL fire rating for roof assembly:** BLOCKER (building code, insurance)
- **Fireproofing thickness below UL listing requirement:** BLOCKER (fire resistance compromised)
- **Missing firestop UL/WHI listing:** BLOCKER (life-safety, fire compartmentalization)
- **Membrane thickness below manufacturer warranty minimum:** BLOCKER (warranty void)
- **NFPA 285 test missing for exterior wall with combustible components:** BLOCKER (fire code)
- **Wind uplift rating below design requirement:** BLOCKER (structural/life-safety)
- **Flame spread exceeds Class A where spec requires:** BLOCKER (fire code)
- **Air leakage rate exceeds spec maximum:** FIX_AND_RESUBMIT (energy code)
- **Sealant movement capability below joint design:** FIX_AND_RESUBMIT (premature failure)
- **Vapor retarder on wrong side of assembly:** BLOCKER (condensation, structural damage)
- **Roofing membrane color mismatch (affects SRI compliance):** BLOCKER if cool roof required, FIX_AND_RESUBMIT if aesthetic only
- **Missing installer certification:** FIX_AND_RESUBMIT (warranty requirement)